Home Health Report

Semi-Annual AC Tune-UpJul 12, 2026

406 Inlet Way, North Palm Beach, FLCare Club · ConnectVisit #1039
71of 100
Action recommended

Gerald, here's how your home is doing

Your system is cooling today, but several indicators came back outside Cassidy's preferred ranges on a 14-year-old unit: the cooling split is low, duct static pressure is high, and the run capacitor measured below its rating. None of these is an emergency. Together, they're worth a proper conversation — we've set up a no-pressure options review with a comfort advisor.

Next: Comfort-advisor options review · Scheduled this week

Score based on Cassidy-defined thresholds for measured performance, component condition, and service history. Drafted with AI assistance; reviewed and approved by your technician.

What we did — photo verified

Condenser · 2012 unit, cabinet corrosion at baseVerified
Condenser · 2012 unit, cabinet corrosion at base
Evaporator coil — heavy buildup, cleaned this visitBefore
Evaporator coil — heavy buildup, cleaned this visit
Run capacitor: 42.3 µF vs 55 µF ratingVerified
Run capacitor: 42.3 µF vs 55 µF rating

System readings

Cooling split (ΔT)13.2 °Ftarget 16–22 °FOut of spec:

Below target — consistent with coil wear and low capacitor output.

Run capacitor42.3 µFtarget 51.7–58.3 µFOut of spec:

Measured well below the 55 µF rating on this unit.

Static pressure0.9 in wctarget < 0.8 in wcWatch:
Compressor amp draw17.8 Atarget < 18.9 AWatch:

Within limit but elevated for this unit's rating.

Follow-up scheduled

Comfort-advisor task created — report, readings, equipment age, and service history attached. A comfort advisor — not a salesperson on commission targets — will walk you through repair and replacement options side by side.

WB
Serviced by Wilkens Baptiste
Senior Comfort Technician · EPA 608 Universal